next up previous contents index
Next: Index Up: No Title Previous: Application Knowledge

  
Problem Description

Part 1: Informal Requirements

Need  PD_1 
Information : This part contains the needs for a new light control system for the fourth floor of building 32 of the University of Kaiserslautern.

Need  PD_2 
Information : The main motivation for the development of a new light control system are the disadvan tages of the currently existing system. Since all lights are controlled manually, electrical energy is wasted by lighting rooms which are not occupied and by little possibilities to adjust light sources relative to need and daylight.

Need  PD_3 
Information : Paragraphs are numbered for easier reference.

1 Needs

Need  PD_4 
Information : In this section, the needs for the new light control system are presented. In 1.1, functional needs are listed and in 1.2 non-functional needs.

1.1 Functional Needs

Need  PD_5 
Information : The functional needs are split into two groups, user needs and facility manager needs, depending on the person who has expressed them.

1.1.1 User Needs

Need  PD_6 
Information : The user needs are numbered by U<number>.

Need  PD_7 
Information : At first, general user needs are listed, which are demanded for each kind of room:

Need  U1 
Information : If a person occupies a room, the light has to be sufficient to move safely, if nothing else is desired by a chosen light scene.

Need  U2 
Information : As long as the room is occupied, the actual chosen light scene has to be maintained.

Need  U3 
Information : If the room is reoccupied within T1 minutes after the last person has left the room, the last chosen light scene has to be reestablished.

Need  U4 
Information : If the room is reoccupied after more than T1 minutes since the last person has left the room, the standard light scene has to be established.

Need  U5 
Information : The wall switches for the window- and the wall-ceiling light group in a room should show the following behavior:
  • if the corresponding ceiling light is completely on, then the light will be switched off
  • otherwise the ceiling light will be switched on completely

Need  U6 
Information : The light scenes can be determined by using the control panel.

Need  U7 
Information : For each room, the actual ambient light level can be set by the user using the control panel.

Need  U8 
Information : For each room, a default light scene can be set (not by using the control panel).

Need  U9 
Information : For each room, a default ambient light level can be set (not by using the control panel).

Need  U10 
Information : The value T1 can be set for each room separately (not by using the control panel).

Need  U11 
Information : If the outdoor light sensor or the motion detector of a room does not work correctly, the user has to be informed.

Need  PD_8 
Information : The user needs concerning the offices are:

Need  U12 
Information : The ceiling lights and the task light should be maintained by the control system depending on different light scenes.

Need  U13 
Information : The control panel should be movable in the offices, like a telephone.

Need  U14 
Information : The control panel should contain at least:
  • a switch to set the task light (on/off)
  • a switch to set the ceiling lights (on/off/ambient)
  • a possibility to set the actual ambient light level

Need  PD_9 
Information : The user needs concerning the remaining rooms are:

Need  U15 
Information : In all other rooms the control panel should be installed near a door to the hallway.

Need  U16 
Information : The control panel should contain at least:
  • a switch to set the ceiling lights (on/off/ambient)
  • a possibility to set the actual ambient light level

Need  PD_10 
Information : The user needs for the hallway sections are:

Need  U17 
Information : When a hallway section is occupied by a person, the light in this hallway section has to be sufficient to move safely.

Need  U18 
Information : Before a person enters one hallway section from another one, the light in the section being entered is turned on if necessary.

Need  U19 
Information : The wall switches for lights in the hallway section have to show the following behavior:
  • if the light is on, then the light will be switched off
  • otherwise the light will be switched on.

1.1.2 Facility Manager Needs

Need  PD_11 
Information : The facility manager needs are numbered by FM<number>.

Need  FM1 
Information : Use daylight to achieve the desired light whenever possible.

Need  FM2 
Information : Lights in a hallway section have to be switched off when the section has been unoccupied for T2 min.

Need  FM3 
Information : If a room is unoccupied for more than T3 minutes, all lights must be switched off.

Need  FM4 
Information : The value T2 can be set for each hallway section separately.

Need  FM5 
Information : The value T3 can be set for each room separately.

Need  FM6 
Information : The facility manager can turn off any light in a room or hallway section that is not occupied.

Need  FM7 
Information : If a malfunction occurs, the facility manager has to be informed.

Need  FM8 
Information : If a malfunction occurs, the control system supports the facility manager by finding the reason.

Need  FM9 
Information : The system provides reports on current and past energy consumption.

Need  FM10 
Information : All malfunctions and unusual conditions are stored and reported on request.

Need  FM11 
Information : Malfunctions that the system cannot detect can be entered manually.

1.2 Non-Functional Needs

Need  PD_12 
Information : The non-functional needs are split into several groups depending on the aspect they are dealing with. They are numbered by NF<number>.

1.2.1 Fault Tolerance

In any case of failure the system shall provide a stepwise degradation of functionality down to manual operability.

Needs in the case of a malfunction of the outdoor light sensor:

Need  PD_13 
Information : In any case of failure the system shall provide a stepwise degradation of functionality down to manual operability.

Need  PD_14 
Information : Needs in the case of a malfunction of the outdoor light sensor:

Need  NF1 
Information : If the outdoor light sensor does not work correctly, the control system for rooms should behave as if the outdoor light sensor had been submitting the last correct measurement of the outdoor light constantly.

Need  NF2 
Information : If the outdoor light sensor does not work correctly, the standard light scene for all rooms is that all ceiling lights are on.

Need  NF3 
Information : If the outdoor light sensor does not work correctly and a hallway section is occupied, the lights in this hallway section has to be on.

Need  PD_15 
Information : Needs in the case of a malfunction of the motion detector:

Need  NF4 
Information : If the motion detector of a room or a hallway section does not work correctly, the control system should behave as if the room or the hallway section mere occupied.

Need  PD_16 
Information : Needs in a worst case failure of the control system:

Need  NF5 
Information : If the lights in a hallway section are neither controllable automatically nor manually, the lights have to be on.

1.2.1 Safety and Legal Aspects

Need  NF6 
Information : All hardware connections have to be made according to DIN standards.

Need  NF7 
Information : No hazardous conditions for persons, inventory, or building are allowed.

1.2.1 User Interface

Need  NF8 
Information : The control panel should be easy and intuitive to use.

Need  NF9 
Information : The system issues warnings on unreasonable inputs.


next up previous contents index
Next: Index Up: No Title Previous: Application Knowledge
Forest-System
1999-06-04